145وصلة كابل كيلوفولت – مصنع

1. ما هو وصلة كابل 145 كيلو فولت؟?

أ 145kV cable joint connects two sections of high-voltage power cables in an underground transmission system. It provides a safe electrical connection and keeps the cable insulation continuous. فضلاً عن ذلك, it protects the connection from moisture, ضرر ميكانيكي, and other external factors.

Power utilities use 145kV cable joints in 110kV and 132kV transmission networks. These systems have a maximum voltage of 145kV. لذلك, each cable joint must match the electrical and mechanical needs of the cable system.

اليوم, many cities and industrial areas use underground power cables instead of overhead lines. نتيجة ل, the demand for reliable 145kV high-voltage cable joints continues to grow.

A high-quality cable joint helps maintain stable power transmission. والأهم من ذلك, it reduces the risk of insulation failure and unexpected power outages.

132كابل كيلو فولت مباشرة من خلال الشركة المصنعة المشتركة

2. Main Types of 145kV Cable Joints

Different power projects require different cable joint designs. The choice mainly depends on cable construction, حجم الموصل, insulation material, وشروط التثبيت.

2.1 145kV Pre-Molded Cable Joint

A 145kV pre-molded cable joint uses a factory-made rubber insulation body. Manufacturers produce this part under controlled conditions to ensure stable dimensions and insulation quality.

أثناء التثبيت, technicians place the pre-molded body over the prepared cable connection. The design provides insulation and controls the electrical field around the conductor connector.

Its main advantages include:

  • Stable insulation quality.
  • Good electrical performance.
  • Compact product design.
  • Faster installation.
  • Reliable long-term operation.

لهذه الأسباب, many underground power transmission projects use pre-molded joints for 110kV, 132كيلو فولت, and 145kV XLPE cables.

2.2 145kV Plug-In Cable Joint

A 145kV plug-in cable joint uses a special plug-in connection structure. It creates a reliable electrical interface between compatible cable components or electrical equipment.

This design offers a clear installation process and helps reduce on-site assembly work. لكن, engineers must check the interface size, هيكل العزل, and electrical rating before selecting the product.

66kV-132kV-145kV-230kV كابل مشترك مستقيم

2.3 145kV Wrapped Cable Joint

A wrapped cable joint uses special insulating tapes and stress-control materials. Technicians build the insulation structure around the cable connection during installation.

This design can meet certain special project needs. لكن, modern 145kV XLPE cable systems often prefer factory-made pre-molded joint solutions because they offer better control over the main insulation structure.

2.4 145kV Transition Cable Joint

A 145kV transition cable joint connects two cables with different designs or insulation systems.

على سبيل المثال, it can connect:

  • XLPE cable to oil-filled cable.
  • XLPE cable to HPFF cable.
  • Copper conductor cable to aluminum conductor cable.
  • Cables with different conductor cross-sections.
  • Cables with different insulation diameters.

في هذه الحالات, engineers must consider conductor connections, insulation compatibility, and electric field control. لذلك, manufacturers should review the complete cable specifications before production.

3. Main Structure of a 145kV XLPE Cable Joint

A typical 145kV XLPE cable joint contains several important parts. Each part has a specific function, and all parts work together to ensure safe operation.

موصل الموصل

The conductor connector joins the copper or aluminum conductors of two cable sections. Manufacturers normally use compression connectors or mechanical connectors.

A good connector provides low electrical resistance and sufficient mechanical strength. فضلاً عن ذلك, its dimensions must match the conductor size.

Main Insulation Body

The main insulation body provides electrical insulation between the conductor and the metallic screen.

Manufacturers commonly use silicone rubber or EPDM materials in pre-molded cable joints. These materials offer good insulation performance and suitable flexibility.

نظام التحكم في الإجهاد

Stress control plays a key role in every 145kV high-voltage cable joint.

When technicians connect two cable sections, the electric field can become uneven around the conductor connector and insulation screen cutback. لذلك, the joint needs a suitable stress-control design.

This system helps distribute electrical stress and reduces the risk of partial discharge.

Semi-Conductive Screen

The semi-conductive screen creates a smooth electrical connection between the cable insulation and the joint insulation system.

It also helps control the electric field around the joint area.

Metallic Shielding

Metallic shielding restores electrical continuity across the cable joint. Manufacturers may use copper wires, copper mesh, or copper tape according to the cable design.

بالإضافة إلى, the metallic screen provides a path for fault current and connects with the cable grounding system.

طبقة الحماية الخارجية

The outer protective layer protects the cable joint from moisture, تآكل, والأضرار الميكانيكية.

For underground installations, waterproof sealing plays an especially important role. نتيجة ل, the joint can maintain reliable performance in different soil and environmental conditions.

66kV-132kV-145kV-230kV كابل مشترك مستقيم

4. Technical Specifications of a 145kV Cable Joint

Before purchasing a 145kV cable joint, customers should confirm the cable voltage rating and construction details.

The following table shows typical application parameters:

المعلمةTypical Specification
جهد الكابل64/110kV or 76/132kV
الحد الأقصى لجهد النظام123kV or 145kV
عزل الكابلاتXLPE
مادة موصلةالنحاس أو الألومنيوم
المقطع العرضي للموصل240-2500 ملم²
Joint typePre-molded or customized
مادة عازلةمطاط السيليكون / إبدم
تثبيتUnderground
شاشة معدنيةCopper wires or copper tape
Main standardاللجنة الانتخابية المستقلة 60840

These values describe common application ranges, not fixed specifications for every product. Actual requirements depend on the cable design and project documents.

على سبيل المثال, a 76/132kV XLPE cable system with a maximum voltage of 145kV needs a compatible 145kV cable joint.

فضلاً عن ذلك, the manufacturer must check the cable insulation diameter, حجم الموصل, screen structure, and outer sheath dimensions before production.

132/230kV Cable Straight Joint Kits

5. 145kV Cable Joint Installation Procedure

Correct installation directly affects the service life of a high-voltage cable joint. Even a well-designed product may fail if technicians do not follow the correct installation process.

لذلك, trained cable jointing technicians should complete the work according to the manufacturer’s installation manual.

خطوة 1: Prepare the Cable Ends

أولاً, technicians measure and mark the cable according to the installation drawings. ثم, they remove the outer sheath, شاشة معدنية, semi-conductive layer, and insulation at the required positions.

They must keep the cable surface clean and avoid damaging the main insulation.

خطوة 2: Connect the Conductors

التالي, technicians connect the two cable conductors with a compression or mechanical connector.

They should follow the specified installation dimensions and tightening requirements. فضلاً عن ذلك, they must check the connector surface and connection quality.

خطوة 3: Install the Main Insulation Body

After completing the conductor connection, technicians install the pre-molded insulation body.

They must place it in the correct position and keep the insulation interface clean. This step helps maintain the required electrical insulation.

خطوة 4: Install the Stress Control Components

Technicians install the stress-control parts according to the manufacturer’s drawings.

Correct positioning is very important because the stress-control system helps prevent high electrical stress around the cable screen cutback.

Submarine Cable Terminal Accessories

خطوة 5: Restore the Metallic Screen

التالي, technicians reconnect the metallic screen across the joint. They also connect the grounding components according to the cable system design.

This step ensures electrical continuity and provides a path for fault current.

خطوة 6: Complete Waterproofing

Technicians install the outer sealing and protective components. These parts prevent water from entering the joint and protect it from external damage.

خطوة 7: Perform Electrical Tests

أخيراً, the project team carries out the required electrical tests and inspections. The team should check the test results before energizing the cable system.

6. Testing Standards for 145kV Cable Joints

Testing helps customers confirm the quality and electrical performance of a 145kV cable joint.

اللجنة الانتخابية المستقلة 60840 covers extruded-insulation power cables and their accessories for rated voltages above 30kV up to 150kV. لذلك, this standard applies to 145kV cable systems.

Depending on the product design and project requirements, the testing program may include:

  • اختبار التفريغ الجزئي.
  • اختبار تحمل جهد التيار المتردد.
  • Lightning impulse voltage test.
  • Heating cycle voltage test.
  • Insulation resistance measurement.
  • Conductor resistance test.
  • التفتيش الميكانيكي.
  • فحص الأبعاد.
  • Sealing and waterproof performance checks.

فضلاً عن ذلك, customers should review the type test reports, routine test records, and quality inspection documents.

Type tests verify the design, while routine tests help control production quality. لهذا السبب, both types of records are important when selecting a 145kV cable joint supplier.

مرفق اختبار كابل DOS

7. Applications of 145kV Cable Joints

145kV cable joints support many high-voltage power transmission projects.

تشمل التطبيقات الشائعة:

  • Underground power transmission networks.
  • High-voltage substations.
  • محطات توليد الطاقة.
  • أنظمة إمدادات الطاقة الصناعية.
  • Solar power transmission projects.
  • Offshore wind farm connections.
  • Urban underground cable networks.
  • Utility grid expansion projects.

For long-distance underground cable circuits, manufacturers cannot always supply one continuous cable length. لذلك, contractors need cable joints to connect different cable sections.

علاوة على ذلك, reliable joints help utilities maintain continuous power transmission and reduce maintenance risks.

8. How to Choose a 145kV Cable Joint Manufacturer?

Choosing the right 145kV cable joint manufacturer is important for project quality and long-term safety.

قبل تقديم الطلب, customers should check the following points.

1. Voltage Compatibility

أولاً, confirm that the cable joint matches the rated voltage and maximum system voltage. For a 145kV system, the joint must meet the electrical requirements of the complete cable circuit.

2. Cable Dimensions

التالي, provide the conductor cross-section, قطر العزل, metallic screen details, and outer sheath dimensions. These details help the manufacturer select the correct joint design.

3. International Standards

Check whether the product meets IEC 60840 and the technical requirements in the project specification.

4. Product Testing

Ask the manufacturer for type test reports, routine test records, and quality documents. These records help verify product performance.

5. دعم التثبيت

A professional supplier should provide installation manuals, technical guidance, and training support when required.

6. Project Experience

أخيراً, check the manufacturer’s experience with 110kV, 132كيلو فولت, and 145kV cable accessories. Previous project experience can help customers assess the supplier’s technical capabilities.

230kV Cable Joint Splices

9. 145kV Cable Joint Manufacturer and Supplier – DOS Group

مجموعة دوس, through Dosense Cable, is a manufacturer and supplier of high-voltage cable accessories in China.

We provide cable joint and cable termination solutions for underground power transmission systems, including 110kV, 132كيلو فولت, and 145kV applications.

Our product range includes:

  • 145kV XLPE cable joints.
  • 145kV pre-molded cable joints.
  • High-voltage cable outdoor terminations.
  • 145kV GIS cable terminations.
  • إنهاء الكابلات الداخلية.
  • High-voltage cable accessories.

We can develop suitable solutions according to the customer’s cable specifications, بما في ذلك المواد الموصلة, منطقة مستعرضة, قطر العزل, metallic screen structure, and rated voltage.

بالإضافة إلى, DOS Group supports technical documentation, product testing, installation manuals, and engineering communication for international power projects.

Whether you are a power utility, مقاول EPC, الشركة المصنعة للكابل, or electrical equipment distributor, we can provide technical support and customized 145kV cable joint solutions.

Contact DOS Group today to request a 145kV cable joint quotation, technical datasheet, مواصفات المنتج, and customized high-voltage cable accessory solutions.